Input voltage:
High voltage tap (400V):340V-5% to 480V=5%
Low voltage tap (110V):90V-5% to 140V+5%
Medium voltage outlet (230V): 200V-5% to 240V+5%
Maximum current for 10s:10A
Internal voltage rheostat:
The voltage can be adjusted using the internal rheostat P1. This rheostat is designed to provide +/-5% adjustment from any voltage within the above voltage ranges.
Remote voltage rheostat:
If necessary, remove the ST10 jumper to connect a remote voltage rheostat.
A 470 Ohms - 3W rheostat can be used for a +/-5% voltage adjustment range or a 1k Ohms - 3W rheostat for a +/-10% voltage range.
An ST1 jumper was included on older R731 modules to increase voltage adjustment range, but was no longer manufactured.
voltage drop
Current sensing: CT for // operation
Location: standard line 1 (U), optional line 2 (V).
- Maximum continuous current: 1.3A
- Rated current: 1A
- Maximum current in 10s: 10A
Voltage drop rheostat:
The P2 rheostat on R731 can be used to adjust the voltage drop. It is designed to provide a minimum voltage drop of 8% at 0 power factor and 1A from the parallel CT.
Spare part for generator sets.
Part/Replacement Number: AUTOMATIC, GENERATOR SET, DETAILS, MAXIMUM, ADJUSTABLE, INTERNAL, RHEOSTAT, RHEOSTAT, DESIGNED, ADJUSTMENT, ST10 JUMPER, CONNECT, ST1 JUMPER, INCLUDED, R731 MODULES, MANUFACTURED, STANDARD LINE, OPTIONAL LINE, CONTINUOUS, NOMINAL, P2 RHEOSTAT, ADJUST, DESIGNED, POWER FACTOR, PARALLEL CONNECTED.