Automatic Voltage Regulator K125-10B for Caterpillar Generator
Article number: K125-10B, K12510B
Specification:
Output power (with a 240Vac input):
10 Adc @ 125 Vdc maximum continuous.
20 Adc @ 250 Vdc boost for 10 seconds.
AC input power:
180 to 280 Vac, single-phase or three-phase, 50 to 400 Hz, 1750 VA maximum continuous load
AC sensing voltage:
90 to 140 Vac, 50/60 Hz; single or three phase.
External voltage adjustment rheostat:
10k ohm, 2W, potentiometer
Control accuracy:
±0.5% answers on average
Voltage operation:
±1% voltage variation for a change of 40°C (104°F).
Response time:
< 4 milliseconds
Frequency compensation:
1 or 2 V/Hz jumper selectable with knee adjustable from 45 Hz to 65 Hz.
EMI attenuation:
Internal filter
Tension build-up:
Internal measures for automatic voltage build-up from generator residual voltages as low as six Vac.
Overexcitation shutdown:
The overexcitation protection starts timing at 180 Vdc ±5% and takes the output to zero in more than 30 seconds. The output can be 250 VDC for more than 10 seconds.
Droop:
1 A or 5 A, <10 VA, Adjustable from 0 to 10% at rated current, 0.8 power factor
UL recognized/CSA certified:
UL recognized under Standard 508, UL File No. E97035. CSA certified under Standard CAN/CSA-C22.2 No. 14-95, CSA File No. LR 23131
Usage: For Caterpillar Generator